The Fiamm 12FLB300 is a 12V 75Ah VRLA (valve regulated lead acid) battery from the high rate ‘Highlite' FLB range of standby batteries which have been developed and optimised to provide a non mains power source in industrial backup equipment such as uninterruptible power supplies (UPS), emergency lighting, telecommunications and security systems. The 12FLB300 guarantees essential building services stay online to support critical system loads and ensures data protection in the event of mains power failure, as part of a battery system this product offers a true ‘peace of mind’ solution for a modern, power reliant industry.
The Fiamm FLB battery catalogue of batteries have been manufactured to very high specifications with flame retardant V0 rated case material a standard feature. Also included are thick grid plates designed to incur minimal corrosion for long service life, insert terminals for simple ‘one tool’ installation and maintenance and with flame arrestors as an additional safety feature. These are just some of the standard features incorporated within the FLB range, and so it is easy to see why so many manufacturers, consultants and facility management engineers insist on choosing the Fiamm FLB range.
As an approved sales parter of Fiamm batteries, we at Blue Box Batteries pride ourselves on excellent client relationships with a first time, on time approach to service. We will always give the best advice possible together with the most competitive pricing available. Call us today for help and support.
RATING | 12V 75Ah |
LENGTH | 261MM |
WIDTH | 174MM |
HEIGHT | 218MM |
WEIGHT | 27KG |
TERMINAL | M8/18 |
SPECIFICATION | Fiamm FLB Range - Previous Model |
SPECIFICATION | Fiamm FLB Range NEW |
DATA SHEET | Fiamm 12FLB300P DATASHEET |
ENGINEERING MANUAL | Fiamm FLB Battery Instructions |
Design Life | 10 year design life (Eurobat Guide - 10-12 years) |
Standard | IEC 60896 Part 21-22, BS6290 Part 4 |
Plates & Grids | Plates and grids designed for optimal short rate discharges. |
Separators | Microporous glass mat allow recombination and fully absorb the electrolyte. |
Terminals | Threaded female M5 terminals provide for high conductivity, maximum torque retention and easy installation. |
Post Seals | State-of-the-art post seals prevent acid seepage over a wide temperature range. |
Safety Valve | Each cell has its own one-way valve. |
Flame Arrestor Device | Expels excess gas while preventing any errant spark or flame from entering the battery. |
Container & Cover | ABS flame retardant plastic in accordance with flame retardancy standard IEC 707 FV0 and UL 94 V0 (LOI greater than 28%). |